Mine flameproof and intrinsically safe DC regulated power , Mine power

KDW127/12B mine explosion-proof and intrinsically safe DC regulated power , also known as: mine power supply, mine explosion-proof uninterruptible power , Mine explosion-proof power , Mine explosion-proof and intrinsically safe DC regulated power. It is a Mine explosion-proof and intrinsically safe type, and is used in places where there is a danger of gas and coal dust explosions in coal mines. Mainly used to provide power for intrinsically safe or explosion-proof and intrinsically safe signal terminals and other

    KDW127/12B mine explosion-proof and intrinsically safe DC regulated power , also known as: mine power supply, mine explosion-proof uninterruptible power , Mine explosion-proof power , Mine explosion-proof and intrinsically safe DC regulated power. It is a Mine explosion-proof and intrinsically safe type, and is used in places where there is a danger of gas and coal dust explosions in coal mines. Mainly used to provide power for intrinsically safe or explosion-proof and intrinsically safe signal terminals and other equipment

  Explosion-proof type: Mine flameproof and intrinsically safe type

  Explosion-proof mark:MbEx db [ib Mb] I Mb

power supply:

  a) Rated working voltage: AC 127V

  b) Power supply voltage fluctuation range:75%~110%

  c)Input apparent power:≤120VA

Main technical parameters:

2-way intrinsically safe 12V DC power output(2 outputs do not share the ground wire):

Serial number

Project

first output

second output

1

Nominal output voltage

12V

12V

2

Rated working current

1.6A

1.6A

3

Maximum open circuit voltage

12.5V

12.5V

4

Overcurrent protection value

1.8A

1.8A

5

Maximum short circuit current

200mA

200mA

6

Periodic and random offset peak-to-peak

250mV

250mV

7

Output voltage deviation value

≤5%

≤5%

8

Source effect

≤5%

≤5%

9

Load effect

≤5%

≤5%

Note::2 outputs do not share the ground wire

Backup Power Features:

    The spare battery pack is powered by five 9856130 lithium manganate batteries in series with protection panels. The nominal voltage of each battery is 3.7V DC and the nominal capacity is 8Ah.

  a) Conversion time:≤300ms

  b) Working Hours:3h

  c) Maximum charging voltage:≤21.5V

  d) Discharge termination voltage:14.0V~16.0V

Function:

  a) The power supply has 2 intrinsically safe 12V DC voltage outputs;

  b) The power supply has the functions of overcurrent protection, overvoltage protection, short circuit protection, and self-recovery function for troubleshooting。



   